technical parameter
Continuum/liquid
 
Measurement Principle: Ultrasound Level Instrument
Characteristic/Application: Integrated Ultrasound Transmitter
Power/Communication: Two-Wire/Four-Wire System (HART), PROFIBUS PA, Foundation Fieldbus (FF)
Measurement accuracy: +/-2 mm or set range +/-0.2%
Ambient temperature: - 20 C... + 80 C (- 40 F... + 176 F)
Process Temperature: - 40 C... + 80 C (- 40 F... + 176 F)
Process Pressure (Absolute Pressure)/Maximum Overpressure Limited Value: 0.7 Bar... 3 Barabs (10 psi... 44 psi), Main Fluid Connection Component PVDF
Process Connection: G/NPT 11/2“
Blind zone distance: 0.25 m (0.8 ft)
Maximum measuring distance: 5 m (16 ft)
Output: 4... 20 mA HART, PROFIBUS PA, Foundation Fieldbus (FF)
Certificate/certification: ATEX, FM, CSA, TIIS, NEPSI
Application limitations: strong chemical corrosion: FMU41/42 / FDU9x, foam / strong disturbance: FMU42 / FDU91, fast feeding / discharging: FMU90 + FDU9x, limit detection: FMU90 + FDU9x
 
technical parameter
Continuum/Solid
Measurement Principle: Ultrasound Level Instrument
Characteristic/Application: Integrated Ultrasound Transmitter
Power/Communication: Two-Wire/Four-Wire System (HART), PROFIBUS PA, Foundation Fieldbus (FF)
Measurement accuracy: +/-2 mm or set range +/-0.2%
Ambient temperature: - 40 degree C... + 80 degree C (- 40 degree F... + 176 degree F)
Process Temperature: - 40 C... + 80 C (- 40 F... + 176 F)
Process pressure (absolute pressure)/maximum overpressure limit: 0.7 bar... 3 bar abs (10 psi... 44 psi)
Main liquid-receiving parts: PVDF
Process Connection: G/NPT 11/2“
Blind zone distance: 0.25 m (0.8 ft)
Maximum measuring distance: 2 m (6 ft)
Output: 4... 20 mA HART, PROFIBUS PA, Foundation Fieldbus (FF)
Certificate/certification: ATEX, FM, CSA, TIIS, NEPSI
Application Limitations: Attention to Measurement Range Graphics
 
 
technical parameter
liquid
Measurement Principle: Ultrasound Level Instrument
Main features: integrated ultrasonic measuring instrument, economical solution
Caliber: unlimited (open channel)
Measurement range: unlimited (measurement distance: 0.25...5 m [0.8...16 ft])
Process Temperature: - 40 C... + 80 C (- 40 F... + 176 F)
Pressure range: atmospheric pressure
Measurement error: low accuracy
Communication: PROFIBUS PA, Foundation Fieldbus (FF)
Output: 4... 20 mA (HART), PA, Foundation Fieldbus (FF)
Input: Two-wire system, 16... 36 V DC, four-wire system, 16... 36 V DC, 90... 253 V AC, 50/60 Hz
Explosion-proof Certification (Ex): ATEX, FM, CSA
Protection Level: IP68