Consultation Hotline:0755-83990550
Ch/En
Localhost:Home > E+H > Location > Guided wave radar >

Levelflex_FMP53

technical parameter
Continuum/liquid
Measuring Principle: Guided Wave Radar Level Instrument
Features/Applications: Premium equipment, hygienic, rod probe, ASME BPE + USP Cl. certification. Built in data storage unit, factory pre calibration, reliable measurement: wave surface + foam surface, medium replacement.
Power/communication: two-wire system (HART, PROFIBUS PA), four-wire system (HART)
Measurement accuracy: rod probe: +/-3 mm (0.12 in)
Ambient temperature: - 40 degree C... + 80 degree C (- 40 degree F... + 176 degree F)
Process Temperature: - 20 C... + 150 C (- 4 F... + 302 F)
Process Pressure (Absolute Pressure) / Maximum Overpressure Limit: Vacuum (...) 16 bar (232 psi)
Main components: rod probe: 304, 304L, 316L, PEEK
Process Connection: Thread: M24
Sanitary process connection: Tri-Clamp clamp, DIN11851, DIN11864-1, NEUMO, Varivent N, SMS
Sensor Length: Rod Probe: 6m (20ft)
Maximum measuring distance: rod probe: 6 m (20 ft); min. DK > 1.6
Output: 4... 20 mA HART, PROFIBUS PA, Foundation Fieldbus (FF)
Certificate/Authentication: ATEX, FM, CSA, CSA C/US, IECEx, NEPSI, WHG Overflow Protection, SIL, EN10204-3.1, 3A, EHEDG, CoC ASME-BPE
Options: split probe with 3 m (9 ft) or 6 m (18 ft) cable
Welded joint