Consultation Hotline:0755-83990550
Ch/En
Localhost:Home > E+H > Location > Capacitive type >

Liquicap_FTI52

technical parameter
Limit/liquid
Measurement Principle: Capacitive Level Measurement
Characteristic/Application: Capacitive Rod Sensor
Ambient temperature: - 50 [C] + 70 [- 58 [F] + 158 [F]), separated shell: - 50 [C] + 120 [- 58 [F] + 248 [F]
Process temperature: - 80 C... + 200 C (- 112 F... + 392 F)
Process Pressure (Absolute Pressure) / Maximum Overpressure Limited Value: Vacuum... 100 bar (1450 psi)
Main components: insulating materials: FEP, PFA, 316L
Process Connection: G 3/4...1/2, NPT 3/4...1/2, Flange: DN25.../ANSI 1".../JIS 10K...
Hygienic process connection: Tri-Clamp ISO02852 clamp with airtight protection, milk pipe connection, safe installation
Sensor Length: Total Sensor Length: Max. 12m (39 ft)
Output: Two-wire system, 19... 253 V, three-wire system, PFM, relay, DPDT, DC-PNP, 8/16 mA
Certificate/Certification: ATEX, FM, CSA, NEPSI, TIIS, SIL, WHG/Overflow Protection, EHEDG/3A, GL Classification Certification
Options: shield length, effective adhesion compensation, separated housing
Characteristics: interface detection and foam detection
Application Limitations: Attention to Pressure and Temperature Change, Attention to DK Value of Non-conductive Medium
Components: Transmitter, PFM: FTC325, FTC625, FTC470Z, FTC471Z, three-wire system: FTC325