Consultation Hotline:0755-83990550
Ch/En
Localhost:Home > E+H > Location > Capacitive type >

Solicap_FTI77

technical parameter
Limit detection/solids
Measuring Principle: Capacitance Level Meter
Characteristic/Application: Full/Semi-insulated Rod/Cable Sensor, Suitable for High Temperature Application and High Mechanical Transverse Load
Power/Communication: 19... 253 V AC, 10... 55 V DC-PNP, 19... 253 V AC and 10... 55 V DC, 8/16 mA, 11... 36 V DC, PFM, three-wire connection
Ambient temperature: - 50 C... 70 C (- 58 F... 158 F)
Process temperature: - 50 C... 400 C (- 58 F... 752 F)
Process Pressure (Absolute Pressure) / Maximum Overpressure Limited Value: Vacuum... 10 bar (145 psi)
Major liquid-receiving components: ceramics, 316L, steel
Maximum Tensile Strength: Cable Sensor: 20 kN
Process connection: R1 1/2, NPT1 1/2 threads, DN/ANSI/JIS flanges
Sensor Length: Cable Sensor: 0.5... 20 m (1.6... 65 ft), Sword Sensor: 0.2... 1 m (0.6... 3.3 ft), shielding length: 0.1... 1 m (0.3... 3.3 ft)
Output: 19-253 V AC, two-wire connection, DC PNP, relay DPDT, PFM, three-wire connection, 8/16 mA
Certificate/Certification: ATEX, FM, CSA, SIL
Characteristics: length of shielding section, automatic adhesion compensation function, strong tension load, strong sensor structure
Application limitation: DK: min 2.5
Instruments: Integrated Instruments and Separate Instruments
Components: PFM: FTC325, FTC625, FTC470Z, FTC471Z, three-wire connection: FTC325