Consultation Hotline:0755-83990550
Ch/En
Localhost:Home > E+H > pressure > Differential pressure transmit >

Deltabar_FMD72

Continuum/liquid
Measurement Principle: Differential Pressure Measurement
Characteristic/Application: Electronic differential pressure measurement Deltabar is used for liquid level measurement in closed pressure system. The system includes sensor module LP, sensor module HP and transmitter. Sensors are sent to transmitters through digital signals. Calculate the differential pressure in the transmitter.
Power/Communication: 4... 20 mA HART
Ambient temperature: - 40 degree C. 80 degrees C (- 40 degrees F (-) 176 degrees F)
Process temperature: - 40 degree C... 125 C (- 40 F.) 257 degrees F)
Contact parts: 316L, Alloc C alloy
Output: 4... 20 mA HART
Certificate/Certification: ATEX FM CSA
Application Limitations: Using Electronic Differential Pressure Selection Software
technical parameter
pressure
Measurement Principle: Differential Pressure Measurement
Characteristic: Deltabar is used for liquid level measurement in closed pressure system. Calculating Liquid Level Based on Static Pressure Measurement and Surface Pressure Measurement in Tank
Power/Communication: 4... 20 mA HART: 12... 45 V DC
Exia: 12... 30 V DC
Measurement accuracy: each sensor: 0.075%
"Platinum type" of each sensor: 0.05%
Long-term stability: 0.05% of URL/year of individual sensor
Process temperature: - 40 C 125 C (- 40 F 257 F)
Ambient temperature: - 40 degree C. 80 degrees C (- 40 degrees F (-) 176 degrees F)
Range of measurement: 400 mbar... 10 bar (6 psi... 150 psi)
Maximum overload limit: 40 bar (600 psi)
Process Connection: Flange: ANSI 2 ", 3"
Thread: MNPT 1/2, FNPT 1/2
Output: 4... 20 mA HART
Certificate/Certification: ATEX, FM, CSA, IECEx NACE MRO 175 EN10204-3.1 Optional four-line digital display stainless steel or aluminum case
Application Limitations: Using Electronic Differential Pressure Selection Software