Cerabar_S_PMC71

technical parameter
Continuum/liquid
Measurement Principle: Static Pressure
Features/Applications: Digital Transmitter, Capacitive Transducer, Ceramic Measuring Diaphragm, Modular Transmitter, High Long-term Stability, Self-diagnostic Function, Effective Safety Improvement, Additional Process Isolation Function
Power/Communication: 4.20 mA HART: 10.5... 45 V DC; Ex ia: 10.5... 30 V DC, PROFIBUS PA / Foundation Fieldbus (FF): 9... 32 V DC
Measurement accuracy: 0.075%, platinum type: 0.05%, long-term stability range upper limit (URL) 0.05% per year
Ambient temperature: - 40 C... 85 C (- 40 F... 185 F)
Process temperature: - 40 C... 150 C (- 40 F) 302 degree F, process pressure (adiabatic pressure)/
Maximum overvoltage limit: 60 bar (900 psi)
Process pressure range: 100 mbar... 40 bar (1.5 psi... 600 psi)
Main liquid-receiving parts: Ceraphire ceramics, Alloy C alloy, 316L, Monel, PVDF
Process connection: thread, flange, Tri-Clamp ISO2852 clamp, sanitary connection
Maximum measuring distance: 400 m (1312 ft) H_2O
Output: 4... 20 mA HART, PROFIBUS PA, Foundation Fieldbus (FF)
Certificate/Certification: ATEX, FM, CSA, TIIS, NEPSI, IECEx, SIL, WHG/Overflow Protection, EN10204-3.1, GL Classification Certification
Options: HistoROM/M-Dat, four-line digital display, stainless steel or aluminium case, separate case
Characteristic: Diagnostic function, multiple operating languages, application limitation measurement unit: ceramic, with pressure, differential pressure measurement can be carried out by two pressure transmitters (electronic differential pressure measurement). Pay attention to the pressure ratio: static pressure.
technical parameter
pressure
Measurement Principle: Static Pressure
Features: Digital transducer, capacitive transducer, ceramic measuring diaphragm, modular transducer, high long-term stability, self-diagnostic function, effectively improve safety, with additional process isolation function
Power/Communication: 4.20 mA HART: 10.5... 45 V DC; Ex ia: 10.5... 30 V DC, PROFIBUS PA / Foundation Fieldbus (FF): 9... 32 V DC
Measurement accuracy: standard type: 0.075%, platinum type: 0.05%.
Long-term stability: 0.05% of maximum range (URL) per year
Process temperature: - 20 degree C... 150 degrees C (- 4 degrees F (-) 257 degrees F)
Ambient temperature: - 40 C... 85 C (- 40 F... 185 F)
Range of measurement: 100 mbar... 40 bar (1.5 psi... 600 psi)
Maximum overvoltage limit: 60 bar (900 psi)
Process Connection: Thread: G1/2... G2, R1/2, MNPT1/2... MNPT2, Flange: DN25... DN80, ASME 1 "... 4", JIS 10K, Sanitary Connection: Tri-Clamp, DIN11851, Varivent N, SMS, DRD
Output: 4... 20 mA HART, PROFIBUS PA, Foundation Fieldbus (FF)
Certificate/Authentication: ATEX, FM, CSA, TIIS, NEPSI, IECEx, SIL, WHG/Overflow Protection, EN10204-3.1, GL Classification Authentication, Options: HistoROM/M-Dat, Four-Line Digital Display, Stainless Steel or Aluminum Shell, Separate Shell
Characteristics: Diagnostic function